RG16H1R12 Single Core 1.8/3kV-26/45kV MV Copper Cable
RG16H1R12 Single Core 1.8/3kV-26/45kV MV Copper Cable

RG16H1R12 Single Core  MV Copper Cable

Voltage:

1.8/3kV  3.6/6kV  6/10kV  8.7/15kV  12/20kV  18/30kV  26/45kV

Structure:

 

 

 

 

 

 

Conductor

class2, compact stranded wire, plain copper

Semiconductor layer

extruded (only cables Uo/U ≥ 6/10 kV)

Insulation

HEPR rubber, G16 quality, Pb free

Semiconductor layer

extruded, cold stripping (only cables Uo/U ≥ 6/10 kV)

Screen

plain copper tapes wrapped

Outer Sheath

PVC based compound, R12 quality

Sheath Colour

red

  • Overview
  • Specifications
  • FAQ
  • Test&Acceptance
  • Send Message

APPLICATION

CHARACTERISTICS

RG16H1R12 Cables are suitable for the transport of energy between the substations and largeusers.For electrical power system in constructions alnd other civil engineeringbulginngs,in order to limit fire and smoke production and spread,in accordance with the CPR For free hanging, pipe or channel. Laying underground also not protected.

Voltage Rating Uo/U

1.8/3kV  3.6/6kV  6/10kV  8.7/15kV  12/20kV  18/30kV  26/45kV

Temperature Rating

Maximun operating temperature:+90°C
Maximun short circuit temperature:+250°C
Min. operating temperature (without mechanical shocks):-15°C

Minimum Bending Radius

12 D

STANDARDS

CEI 20-13, HD 620 IEC 60502pqa

EN 50575:2014 + EN 50575/A1:2016 (IEC 60332-1-2)

CONSTRUCTION

Conductor

class2, compact stranded wire, plain copper

Semiconductor layer

extruded (only cables Uo/U ≥ 6/10 kV)

Insulation

HEPR rubber, G16 quality, Pb free

Semiconductor layer

extruded, cold stripping (only cables Uo/U ≥ 6/10 kV)

Screen

plain copper tapes wrapped

Outer Sheath

PVC based compound, R12 quality

Sheath Colour

red

THE CABLE TEST

We have world-class testing facility, and made rigorous testing regime, every meter of cable before leaving the factory must go through strict testing, testing qualified products will be shipped to customers, effectively ensure product quality and meet customer requirements.

SUSTAINABILITY COMMITMENT

Guowang Cable actively implements the "carbon reduction" goal, strives to promote the green's low-carbon transformation, strengthens energy-saving and emission reduction technology innovation, and promotes the company's healthy and sustain-able development.

Rated Voltage Formation Approx. conductor Ø Average insulation thickness     Approx.     external         Ø Approx. cable weight Current rating A
in air buried*
1.8/3kV n° x mm2 mm mm mm kg/km trefoil flat trefoil flat
1 x 10 4 2 12.8 300 87 111 99 104
1 x 16 4.8 2 13.6 365 114 145 126 133
1 x 25 6 2 14.8 470 149 190 162 171
1 x 35 7 2 15.9 580 181 230 193 204
1 x 50 8.1 2 17 700 219 276 227 241
1 x 70 9.7 2 18.6 920 275 345 278 294
1 x 95 11.4 2 20.3 1190 339 422 332 351
1 x 120 12.9 2 21.9 1440 393 487 377 399
1 x 150 14.3 2 23.3 1720 446 550 421 445
1 x 185 16 2 25 2065 516 635 477 500
1 x 240 18.3 2 27.1 2640 617 745 550 580
1 x 300 21 2 30.1 3310 709 855 621 650
1 x 400 23.2 2 32.5 4125 824 990 702 735
1 x 500 26.1 2.2 36.7 5250 954 1140 790 830
1 x 630 30.3 2.4 41.1 6760 1102 1300 885 930
3.6/6kV 1 x 10 4 3 14.8 365 87 105 95 100
1 x 16 4.8 3 15.6 435 113 136 122 128
1 x 25 6 3 16.8 550 150 180 156 165
1 x 35 7 3 17.9 660 182 220 187 197
1 x 50 8.1 3 19 795 219 261 220 233
1 x 70 9.7 3 20.6 1015 275 328 271 286
1 x 95 11.4 3 22.3 1295 337 402 324 342
1 x 120 12.9 3 23.9 1550 390 465 370 390
1 x 150 14.3 3 25.3 1840 443 525 412 435
1 x 185 16 3 27 2190 512 605 468 491
1 x 240 18.3 3 29.3 2790 608 715 540 570
1 x 300 21 3 32.3 3465 700 820 610 640
1 x 400 23.2 3 34.7 4280 813 950 690 725
1 x 500 26.1 3.2 38.9 5430 940 1100 780 820
1 x 630 30.3 3.2 42.7 6910 1082 1260 875 915
6/10kV 1 x 10 4 3.4 18.6 460 91 105 93 98
1 x 16 4.8 3.4 19.4 535 117 136 120 128
1 x 25 6 3.4 20.6 650 154 178 155 163
1 x 35 7 3.4 21.6 760 186 219 185 195
1 x 50 8.1 3.4 22.7 905 223 260 218 231
1 x 70 9.7 3.4 24.3 1190 279 325 270 285
1 x 95 11.4 3.4 26 1420 340 398 320 340
1 x 120 12.9 3.4 27.8 1695 395 460 365 385
1 x 150 14.3 3.4 29.4 2015 448 520 410 432
1 x 185 16 3.4 31.1 2380 516 600 464 490
1 x 240 18.3 3.4 33.9 3015 610 705 540 565
1 x 300 21 3.4 36.6 3705 703 810 605 635
1 x 400 23.2 3.4 39.8 4595 815 935 690 720
1 x 500 26.1 3.4 43.4 5740 945 1080 780 810
1 x 630 30.3 3.4 47.7 7280 1085 1230 875 900
8.7/15kV 1 x 16 4.8 4.5 21.6 620 120 135 118 123
1 x 25 6 4.5 22.8 745 155 177 152 158
1 x 35 7 4.5 23.8 865 190 215 181 190
1 x 50 8.1 4.5 24.9 1010 225 258 213 224
1 x 70 9.7 4.5 26.5 1250 282 323 262 276
1 x 95 11.4 4.5 28.2 1540 345 393 313 330
1 x 120 12.9 4.5 30.2 1840 400 455 358 375
1 x 150 14.3 4.5 31.8 2170 450 515 396 420
1 x 185 16 4.5 33.7 2550 518 590 453 475
1 x 240 18.3 4.5 36.3 3190 615 700 525 550
1 x 300 21 4.5 39.4 3930 704 800 590 620
1 x 400 23.2 4.5 42.2 4805 816 920 670 700
1 x 500 26.1 4.5 45.8 5950 945 1060 760 785
1 x 630 30.3 4.5 49.9 7505 1088 1210 850 870
12/20kV 1 x 25 6 5.5 24.8 840 158 176 153 158
1 x 35 7 5.5 25.8 965 190 213 182 189
1 x 50 8.1 5.5 26.9 1120 230 255 216 225
1 x 70 9.7 5.5 28.5 1365 285 320 265 275
1 x 95 11.4 5.5 30.4 1680 348 390 315 329
1 x 120 12.9 5.5 32.6 2000 400 450 360 374
1 x 150 14.3 5.5 34.1 2320 450 510 402 416
1 x 185 16 5.5 35.9 2710 520 585 455 472
1 x 240 18.3 5.5 38.9 3395 615 690 528 545
1 x 300 21 5.5 41.6 4110 705 790 595 611
1 x 400 23.2 5.5 44.2 4980 815 910 674 690
1 x 500 26.1 5.5 48 6175 945 1050 762 776
1 x 630 30.3 5.5 52.1 7740 1087 1190 858 875
18/30kV 1 x 35 7 8 31 1310 191 212 182 188
1 x 50 8.1 8 32.5 1470 229 254 214 222
1 x 70 9.7 8 34.1 1730 285 316 263 272
1 x 95 11.4 8 36 2065 347 387 314 325
1 x 120 12.9 8 38.4 2425 401 445 358 370
1 x 150 14.3 8 39.9 2760 452 505 400 415
1 x 185 16 8 41.7 3105 520 580 453 469
1 x 240 18.3 8 44.3 3860 615 680 525 540
1 x 300 21 8 46.8 4585 705 775 593 606
1 x 400 23.2 8 49.6 5505 815 895 671 685
1 x 500 26.1 8 53.4 6745 943 1030 761 775
1 x 630 30.3 8 57.5 8345 1085 1170 860 875
26/45kV 1 x 70 9.7 10.3 39.3 2190 280 315 255 260
1 x 95 11.4 10.3 41.2 2540 340 380 300 310
1 x 120 12.9 10 42.2 2805 395 440 355 365
1 x 150 14.3 9.5 42.8 3080 445 495 385 395
1 x 185 16 9.3 44.3 3465 510 570 440 450
1 x 240 18.3 9.3 46.9 4160 600 665 510 520
1 x 300 21 9 49.2 4875 695 760 570 580
1 x 400 23.2 9 51.8 5782 800 875 650 655
1 x 500 26.1 9 55.3 7000 930 1010 735 740
1 x 630 30.3 9 59.3 8355 1070 1180 835 845
  • Who we are?

    We are based in Henan, China, start from 2012,sell to Domestic Market(70.00%), Mid East(11.00%), South America(10.00%), Africa(3.00%), North America(2.00%), Southeast Asia(2.00%), Eastern Asia(00.00%), South Asia(00.00%). There are total about 101-200 people in our office.

  • How can we guarantee quality?

    Always a pre-production sample before mass production; Always final Inspection before shipment.

  • What can you buy from us?

    Wire, Cable

  • Why should you buy from us not from other suppliers?

    We have twenty years of experience in design and development

  • What services can we provide?

    Accepted Delivery Terms: FOB,CFR,CIF,EXW;
    Accepted Payment Currency: USD,EUR;
    Accepted Payment Type: T/T,L/C,Money Gram,Western Union;
    Language Spoken: English,Chinese,French

  • How long does it take to get a quote back?

    Most quotes are returned within 24 hours

Test

Cable tests are divided into ex-factory test and type test.

1.EX-factory test

Ex-factory inspection includes 100% inspection and sampling inspection.

100% inspection items: conductor resistance measurement; Partial discharge test; Voltage test.

Sampling inspection shall be carried out on the cable after 100% inspection items have been completed and passed.

Sampling inspection items: Concentricity of insulation: Conductor inspection; Dimensional inspection; Voltage test; Thermal extension test of XLPE insulation.

2.Type test

Type test sample cables should be randomly selected from the cables that have passed the factory inspection.

Electrical type test items: bending test and subsequent partial discharge test; Tan delta measurement; Thermal cycle test and subsequent partial discharge test; Impulse voltage test and subsequent power frequency voltage test; 4h voltage test.

Non-electrical type test items: measurement of insulation thickness; Measurement of non-metal sheath thickness; Mechanical properties test before and after insulation aging; Mechanical properties test of non-metal sheath before and after aging; Additional aging tests for finished cable segments; ST2 type PVC sheath weight loss test; High temperature pressure test of insulation and non-metal sheathing; Low temperature performance test of PVC sheath; Cracking resistance test of PVC sheath (thermal shock test); Insulation water absorption test; Non-flame delay test of single cable; XLPE insulation shrinkage test; Strippability test of insulation shield; Water permeation test.

Product performance requirements and test methods are in accordance with the provisions of standard GB/T 12706.3-2008.

Check and accept

1.The purpose of the performance acceptance test is to check whether all the properties of the contract products meet the requirements.

2.The site of performance acceptance test shall be the demander's site.

3.The performance acceptance test shall be carried out within 6 months after the 168-hour full load trial operation of the product, and the specific test time shall be determined by both parties through negotiation.

4.Installation of measuring points, primary components and local instruments required for performance acceptance test shall be provided by the supplier and cooperated by the demander. The supplier shall also provide the technical cooperation and personnel cooperation required for the test.

5.Content of performance acceptance test

In accordance with supplier quality assurance and test requirements.

6.Criteria for performance acceptance test

In accordance with supplier's quality assurance and test requirements.

7.The performance acceptance test shall be conducted by the demander and participated by the supplier. The test program shall be provided by the demander and determined after discussion with the supplier. The specific test shall be completed by the testing department approved by both parties.

8.Confirmation of performance acceptance test results

The performance acceptance test report shall be prepared by the testing unit, and the conclusions of the report shall be accepted by both parties. If there is any disagreement between the two parties on the results of the test, the two parties shall settle it through negotiation. If no agreement can be reached, it shall be submitted to the superior departments of both parties for negotiation.

9.When a performance acceptance test is conducted, if a party fails to send personnel to participate in the test after receiving the test notice from the other party, it shall be deemed to have agreed to the acceptance test results.

Supervision

1.Basis of supervision  

Reference to the former Ministry of Electric Power Industry, Ministry of Machinery Industry issued by the Office (1995) No. 37 document "Interim Provisions on Quality Supervision of Large Electric Power Equipment" , "Regulations on the Work of the General Representative Group in Large Electrical Equipment Manufacturing Plants".

Reference to DL/T 586-2008 "Technical Guidelines for Equipment Manufacturing Supervision".

GB/T 50319-2013 "Specifications for Construction Project Supervision", GB/T 19000-2016/ISO 9000:2015 "Quality Management and Quality Assurance" Standard.

The relevant commercial terms and technical agreements in the equipment purchase contract signed between the user and the manufacturer, including legally binding documents, letters, correspondence, etc.

Product equipment drawings confirmed by the user and the manufacturer and modification notice issued by the design unit.

National standards, industry standards, and enterprise standards involved in technical documents and design drawings (subject to the latest version). If the standards adopted by the technical documents and the design drawings are inconsistent with each other, the national standards, industry standards, and enterprise standards shall be adopted as the recurrence order.

When the design drawing is inconsistent with the referenced standard, the requirements in the standard shall prevail in principle, except for those with special requirements for parts.

2.Supervision method

Document witness, site witness and stoppage for inspection, namely R point, W point, H point.

Each time after the completion of the supervision content, the supplier and the supervision representative will perform the signature procedure on the witness form. The supplier shall deliver one copy to the demand's supervision representative.

R Point : The supplier only needs to provide items of inspection or test records or reports, that is, document witness.

W Point : Inspection or test items attended by the purchaser’s manufacturing supervision representative, that is, on-site witness.

H Point : The supplier stops work at this point to wait for inspection or testing by the demander's manufacturing supervision representative, that is, it stops work pending inspection.

After receiving the witness notice, the demander shall promptly send representatives to the supplier's inspection or testing site to participate in on-site witnessing or stop work pending inspection.If the demander's representative cannot attend on time, point W can be automatically converted to point H, but if point h is converted to point r without the demander's written notice, the supplier will not transfer to the next process and agree with the demander to change the witness time.If the buyer is still unable to participate on time after the change, the H point will be automatically converted to R point.

3.Requirements for Supplier's Cooperation in Manufacturing Supervision

The supplier has the obligation to cooperate with the demander's manufacturing supervision and provide relevant information in a timely manner without incurring any costs.

The supplier shall provide the demander's supervision representative with convenience in work and life.

The supplier shall inform the representative of the buyer of the equipment supervision project and time before on-site witness or stopping work for inspection.

The demander's supervision representative has the right to check (borrow) the technical data related to the contract supervision equipment. If the demander deems it necessary to copy and file, the supplier shall provide convenience.

After witnessing, the supplier shall provide relevant inspection, test records and report data to the manufacturing supervision representative of the demander.